Back

Intelligent Manual Call Point (Red)

Product code: SA5900-908APO

SA5900-908APO - Intelligent Manual Call Point (Red)
The Intelligent Manual Call Point has been designed to operate on a loop of intelligent fire detection devices. An alarm is initiated by pressing the resettable element. The manual call point signals to the Control and Indicating Equipment using an interrupt feature within the Apollo Digital Protocol. An alarm status is indicated through the rotation of the resettable element, displaying yellow and black indication bars and a solid red LED. The manual call point can be easily reset from the front using the supplied reset key.
Full details
Electrical Considerations

The Intelligent Manual Call Point is loop powered and operates at 17-35V DC for all variants.

Operating Principles

The address of each call point is set at the commissioning stage by means of a DIL switch. A solid red alarm LED is provided on the manual call point. This LED is controlled independently of the call point, by the control panel. The LED will flash yellow if there is a fault and flash green when the device is polled. Discovery and CoreProtocol configurable. Once activated, the Intelligent Manual Call Point can be reset by inserting the reset key into the front facing LED, turning clockwise until a positive click and reset occurs. The Intelligent Manual Call Point incorporates a short circuit isolator which will ensure its operation in the event of a short circuit fault on the loop. Isolator operation is indicated by a solid yellow LED. For further details of the isolator refer to data sheet PP2090, available on request. This manual call point helps reduce installation time as all the initial installation cabling is wired to a removable terminal block which fits neatly in the back of the manual call point.

Mechanical Construction

The component parts of the call point are moulded in a robust fire retardant polycarbonate.

Backward Compatibility

The Intelligent Manual Call Point will operate with compatible Apollo control equipment using the digital XP95, Discovery and CoreProtocols.

EMC Directive 2004/108/EC

The Intelligent Manual Call Point complies with the essential requirements of the EMC Directive 2004/108/EC, provided that it is used as described in this data sheet. A copy of the Declaration of Conformity is available from Apollo on request. Conformity of the Intelligent Manual Call Point with the EMC Directive does not confer compliance with the directive on any apparatus or systems connected to it.

Construction products regulation 305/2011

The Intelligent Manual Call Point complies with the essential requirements of the Construction Products Regulation 305/2011. A copy of the Declaration of Performance is available from Apollo on request.

Product Information

The Intelligent Manual Call Point has been designed to operate on a loop of intelligent fire detection devices. An alarm is initiated by pressing the resettable element. The manual call point signals to the Control and Indicating Equipment using an interrupt feature within the Apollo Digital Protocol. An alarm status is indicated through the rotation of the resettable element, displaying yellow and black indication bars and a solid red LED. The manual call point can be easily reset from the front using the supplied reset key.

Key Features

Resettable operating element Easy access, front reset mechanism E-Z fit connector system for installation Ergonomic reset key EN 54-11 & EN 54-17 Certified (Red version only) 170° viewable LED Continuity link for cable insulation testing Suitable for semi flush or surface mounting

General
Warranty10 year
Performance
Analogue value nominal16
Alarm level analogue value64
Fault level analogue value4
TypeA
Operating elementResettable element
ActionSingle
Electrical
Protocol voltage (min)5V
Protocol voltage (max)13V
Protocol voltage5 to 13V peak to peak
Power-up surge current 1mA
Maximum power-up time1 second
Quiescent current100μA
Quiescent current tested at24V dc
Supply voltage (min)17V dc
Supply voltage (max)35V dc
Supply voltage (Vmin-Vmax)17 to 35V dc
Alarm current (at 24 volts)4mA
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-40°F
Operating temperature (max)158°F
Operating temperature-40 to 158°F
IP rating ValueIP44
Conformance
Standards
  • EN 54-11
  • EN 54-17
Approvals
  • SBSC
  • VdS
  • CPR
  • FG
  • LPCB
Mechanical
Weight180g
ColourRed
Materials housingPolycarbonate
Product length3.54in
Product width3.54in
Product depth2.48in
Key typeApollo Manal Call Point reset key
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.