Back

Soteria Heat Detector (Isolated)

Product code: SA5100-400RUS

SA5100-400RUS - Soteria Heat Detector (Isolated)
The Soteria Heat Detector features two heat sensors located laterally to ensure accurate heat detection in all orientations.
Full details

Application environments

Car parks/loading bays

Warehouses

Electrical Considerations

The Soteria detector is designed to be connected to a two-wire loop circuit carrying both data and power. A version with a short-circuit isolator integrated into the detector head is also available.

Operating Principles

The low profile design of the Soteria Heat Detector is sleek and evolutionary, with a 360° LED indicator which illuminates red when in alarm, yellow to indicate a fault and green to indicate protocol activity. • Dual heat sensors to ensure a accurate response in all orientations • Seven operating modes (Mode 8 not used) Heat detector classifications are defined by EN 54-5 as shown in Table 1, each class specifies an application temperature and a static response temperature. Application temperatures define the environmental temperatures the detector can be expected to experience in non-fire conditions. Classes should be selected so that the maximum application temperature is not exceeded. The static response temperature indicates the temperature which the device will produce an alarm signal. In addition to the basic classification a detector may be given an “R” or “S” suffix. The “R” suffix indicates that the detector has been designed to have a rate-of-rise characteristic. “R” suffix detectors will produce an alarm signal when exposed to a rapid temperature increase. Slower temperature rises will not generate an alarm unless they exceed the static response temperature. A “R” suffix detector will therefore give a rapid fire response even when starting from an ambient temperature well below its typical application temperature. The “S” suffix indicates that the detector will not produce an alarm signal below its minimum static response temperature even when exposed to high rates of rise of air temperature. Soteria Heat Detectors have seven available modes which correspond to seven “classes” as defined in EN 54-5. To ensure backwards compatibility, Modes 1 to 5 inclusive are identical to the modes used in Discovery Heat Detectors. Modes 6, and 7 provide additional heat detector classes and are exclusively available to CoreProtocol enabled fire control panels. Each class corresponds to a different response behaviour and is designed to be suitable for a range of application temperatures and fire risks.

Application

Fire detectors should always be installed in accordance with all local and national laws and codes of practice. A “R” suffix detector is suitable for areas such as unheated warehouses in which the ambient temperature may be very low for long periods. A “S” suffix detector is suitable for areas such as kitchens and boiler rooms, where large rapid temperature changes are considered normal.

Device Addressing

A universal XPERT 8 card is supplied with all XPERT 8 Intelligent Mounting Bases. Using a coding guide, pips on the card are removed to set the address of the detector. This simplifies and speeds up installation, commissioning and maintenance. The address location remains the same no matter how often detectors are replaced. When Soteria devices are used with CoreProtocol, device auto-addressing can be enabled by fire control panels that have been designed to incorporate this feature.

Communication

Soteria uses the new digital CoreProtocol to allow more advanced control and configuration, whilst maintaining backwards compatibility with previous generations of Apollo products – XP95 and Discovery. Discovery and CoreProtocol make use of the Normal, Read and Write modes with additional non-volatile data fields made available to the fire control panel.

Backward Compatibility

Soteria detectors have been designed to operate on XP95 and Discovery loops. This allows for Soteria detectors and bases to operate on existing systems and for Soteria detectors to operate on XP95 and Discovery bases (XPERT 7 Intelligent Mounting Base). It should be noted that not all features of Soteria will be available when used with XP95 or Discovery fire control panels. If Soteria detectors are used with XP95 fire control panels incorporating drift compensation algorithms, these must be disabled when communicating with Soteria devices. When Soteria detectors are used with an XPERT 7 Intelligent Mounting Base on a CoreProtocol system, Soteria devices will have a +128 address offset due to only 7 address pips being available on the XPERT 7 card. For example, an XPERT 7 card set at 32 will address as 160 on CoreProtocol with Soteria detectors.

Maintenance & Service

Soteria detectors have been designed with a comprehensive set of features to support maintenance and service, from self test capabilities to drift compensation warnings on dirty detectors. The new FasTest® mode facility on Soteria can be enabled within a fire control panel that incorporates this feature. This facilitates quicker testing of detectors with appropriate test equipment. FasTest disables the transient rejection algorithms to allow a faster detector response, whilst ensuring the detectors absolute sensitivity remains identical to mode 3. A visual pass/fail indication is provided by the detector and overall, FasTest reduces commissioning and maintenance time. Maintenance has to be performed in accordance with all applicable standards. Clean the detector externally using a soft damp cloth. For full cleaning and recalibration detectors should be returned to Apollo Fire Detectors.

EMC Directive 2004/108/EC

The Soteria Heat Detector complies with the essential requirements of the EMC Directive 2004/108/EC, provided that it is used as described in this datasheet. A copy of the Declaration of Conformity is available from Apollo on request. Conformity of the Soteria Heat Detector with the EMC Directive does not confer compliance with the directive on any apparatus or systems connected to it.

Construction products regulation 305/2011

The Soteria Heat Detector complies with the essential requirements of the Construction Products Regulation 305/2011. A copy of the Declaration of Performance is available from Apollo on request.

Product Information

The Soteria Heat Detector features two heat sensors located laterally to ensure accurate heat detection in all orientations.

Key Features

Dual heat sensors Utilises digital CoreProtocol communications Compatible with XP95 and Discovery systems* Mechanically compatible with existing bases Available with or without integrated switchable isolator Tri-coloured LED status indicator Polycarbonate moulding for colour stability and strength Comprehensively tested to exceed EN 54-5 standard FasTest® for quicker testing of detectors XPERT 8 card addressing Locking mechanism (grub screw) * Note: Not all features are available when Soteria devices are connected to an XP95 or Discovery fire control panel

General
Applications
  • Car parks/loading bays
  • Warehouses
Warranty10 year
Performance
Heat classification
  • A1R
  • A2R
  • A2S
  • BR
  • BS
  • CR
  • CS
Electrical
Protocol voltage (min)5V
Protocol voltage (max)13V
Protocol voltage5 to 13V peak to peak
Power-up surge current 560mA
Status indicator - AlarmRed
Status indicator - FaultFlashing yellow
Status indicator - IsolateYellow
Status indicator - PollGreen
Quiescent current300μA
Quiescent current tested at24V dc
Terminal functions L2+L2 Loop in & out positive
Terminal functions L1 in-L1 in Loop (isolated) negative
Terminal functions L2 out-L1 out Loop (isolated) negative
Terminal functions +R+R Remote indicator positive connection
Terminal functions -R-R Remote indicator negative connection
PolarityL1 & L2 are polarity sensitive
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-40°F
Operating temperature (max)158°F
Operating temperature-40 to 158°F
IP rating ValueIP54
Conformance
Standards
  • EN 54-5
  • EN 54-17
ApprovalsVNIIPO
Mechanical
Weight83g
ColourWhite
FinishGloss
Materials housingPolycarbonate
Materials terminalsTin plated stainless steel
Product diameter3.94in
Detection principleTemperature sensitive resistance.
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.