55000-280APO - Intelligent IR² Flame Detector
The Intelligent IR² Flame Detector is designed for use in areas where flaming fires may be expected. The detector has two sensors which respond to different IR wavelengths to discriminate between flames and spurious sources of radiation. Applications include aircraft hangars, coal handling and paper manufacturing plants and woodworking environments.
Full Details
Electrical Description

The Intelligent IR2 Flame Detector is loop powered and needs no external supply. A remote LED alarm indicator may be connected to the flame detector.

Operation

The IR2 Flame Detector is sensitive to low-frequency, flickering infra-red radiation emitted by flames during combustion. Since it responds to flickering radiation the IR2 Flame Detector can operate even if the lens is contaminated by a layer of oil, dust, water-vapour or ice. The IR2 Flame Detector is set to respond to low-frequency radiation at 1 to 15Hz (1 to 2.7μm) in order to detect all flickering flames, including those invisible to the naked eye, eg, those emitted by hydrogen fires. The IR2 Flame Detector has two IR sensors that respond to different IR wavelengths in order to discriminate between flames and spurious sources of radiation. False alarms due to such factors as flickering lighting are avoided by a combination of filters and signal processing techniques.

Backward Compatibility

The Intelligent Flameproof IR2 Flame Detector operates only with control equipment using the Apollo XP95 or Discovery digital protocol (or any development of it).

Maintenance & Service

The flame detector is designed to give years of trouble-free operation with minimal attention. However the periodic maintenance steps listed below are essential to maintain reliable fire protection. 1. Inform all appropriate personnel of intention to work on the flame detector. 2. Disable any automatic systems that may be activated by the flame detector if not required as part of the maintenance check. 3. Check that the flame detector’s control panel is functioning correctly and shows no faults. 4. Inspect the detector viewing window for any build-up of dust or other contaminants on the optical surface. If necessary clean the optical surface with a cotton wipe wet with commercial liquid glass cleaner. Rinse with clean water and dry with a clean cloth. The detector specification for performance is with a clean optical sensor window. Contaminants like dust, oil and paint will reduce sensitivity. 5. Ensure the detector still has a clear line of sight of the area it is protecting and no obstacles obstruct its view. 6. Check that the detector is securely fitted. 7. Visually check the exterior of the detector for any mechanical or corrosive damage. 8. Test the operation of the detector with either a portable flame sensor test unit or if practical a flickering yellow flame. 9. Reinstate any automatic system disabled during maintenance. 10. Inform all appropriate personnel on completion of the maintenance work and if necessary record this work.

Additional Information

ACCESSORIES A range of accessories and test equipment is available for the Intelligent Flameproof IR2 Flame Detector: Weathershield, part no 29600-228, Flame Sensor Test Unit and case, part no 29600-226.Stainless steel 2 axis adjustable mounting bracket, part no 29600-203 * For a full list of applications for Apollo Flame Detectors, please refer to PP2409, available on request.

Product Information

The Intelligent IR² Flame Detector is designed for use in areas where flaming fires may be expected. The detector has two sensors which respond to different IR wavelengths to discriminate between flames and spurious sources of radiation. Applications include aircraft hangars, coal handling and paper manufacturing plants and woodworking environments.

Key Features

Sensitive to flickering IR radiation Detects through films of oil, dust, water and ice Responds to flickering flames, including those invisible to the naked eye Compatible with Discovery and XP95 protocols Remote optical self-test function 90° field of view Up to 40m coverage

General
Warranty10 year
Performance
Range of view (at 25m)0.1m² n-heptane
Range of view (at 35m)0.2m² n-heptane
Range of view (at 45m)0.4m² n-heptane
Field of view90°
Sensitivity
  • High-Class 1
  • Low-Class 3
Electrical
Maximum power-up time4 seconds
Quiescent current2200μA
Supply voltage (min)17V dc
Supply voltage (max)28V dc
Supply voltage (Vmin-Vmax)17 to 28V dc
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-10°C
Operating temperature (max)55°C
Operating temperature-10 to 55°C
IP rating ValueIP65
Storage temperature (min)-20°C
Storage temperature (max)65°C
Storage temperature-20 to 65°C
Conformance
Approvals
  • CCMG
  • CPR
  • FG
  • LPCB
Mechanical
Weight1000g
ColourBlue
Materials housingDie-cast zinc alloy
Product length142mm
Product width108mm
Product depth82mm
Number of cable gland entries2
Cable gland entries size20mm
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.