Back

Three Channel Input/Output Module

Product code: 55000-588APO

55000-588APO - Three Channel Input/Output Module
The Three Channel Input/Output Module provides three voltage-free, single pole, change/over relay outputs and three monitored switch inputs.
Full Details
Electrical Description

The Three Channel Input/Output Module is loop powered and operates at 17–28V DC with protocol voltage pulses of 5–9V.

Operation

The Three Channel Input/Output Module supervises one or more normally-open switches on each of the three inputs. It is set to return an analogue value of four in the event of an open or short-circuit fault and 16 during normal operation. The status of the inputs is reported by three input bits. The change-over contacts of each relay are operated by three command bits. Ten LEDs, six red and four yellow, are fitted to the PCB. All LEDs except the isolator LED can be disabled to conserve loop current. The LEDs are disabled using the eighth segment of the DIL switch. For each channel, one red LED is illuminated to indicate that the relay is set; a second red LED is illuminated to indicate that the switch input is closed and a yellow LED is illuminated to indicate an open or short-circuit fault. A separate yellow LED is illuminated whenever the built-in isolator has sensed a short-circuit loop fault. It is recommended that the LEDs are disabled for normal operation.

Mechanical Construction

Dimensions and weight: 250 x 175 x 75mm 621g (in enclosure) 140 x 160 x 18mm 111g (PCB only)

Backward Compatibility

The module will operate only with control equipment using Apollo XP95 or Discovery protocol. It may also be used to replace earlier Series 90 Three Channel Input/Output Units.

Product Information

The Three Channel Input/Output Module provides three voltage-free, single pole, change/over relay outputs and three monitored switch inputs.

Key Features

Uses a single address Individually monitored inputs Built-in isolator Flexible installation - cable entry knockouts on all four sides

General
Warranty10 year
Electrical
Protocol voltage (min)5V
Protocol voltage (max)9V
Protocol voltage5 to 9V peak to peak
Power-up surge current 6.5mA
Maximum power-up time150ms
Maximum continuous current1A
On resistance0.2Ω
Switch input monitoring voltage (min)9V dc
Switch input monitoring voltage (max)11V dc
Switch input monitoring voltage9 to 11V dc
Maximum cable resistance50Ω
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-20°C
Operating temperature (max)70°C
Operating temperature-20 to 70°C
IP rating ValueIP54
Conformance
Approvals
  • CPR
  • VdS
  • LPCB
Mechanical
ColourWhite
Relay output contact rating1A
Relay output rating tested at30V ac
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.