Full Details
Electrical Description

All devices are powered directly from the loop and need no external power supply. They operate at 17–28V DC and are polarity sensitive.

Operation

A nominal sound output of 100dB(A) is achieved at a current consumption of 5mA in the case of the sounder and 8mA for the sounder beacon. Many control panels will be able to drive up to 20 sounders and up to 15 sounder beacons per loop on average. The maximum number of devices that may be connected to a particular loop should, however, be determined by a loop loading calculation using the Apollo Loop Calculator. This is available via the Apollo website www.apollo-fire.co.uk. Since the alarm devices are intended for use in open areas, it is possible for more than one device to be audible at any given point in a building. For this reason, the operation of all may be synchronised by the control panel. All the alarm devices can be assigned group addresses as well as individual addresses, so that the functional options of the sounder are identical with those of the Sounder Control Unit part no 55000-582 or 55000-182 (DIN-rail version).

Mechanical Construction

The alarm devices have a base which is fitted to the mounting surface and wired as a 'first fix'.

Device Addressing

The open-area alarm devices respond to their own individual address set with a DIL switch. They can also respond to a 'Group Address' which allows multiple sounders to be controlled simultaneously. A group address may be any spare address between 112 and 126 and is selected by means of a 4 segment DIL switch. A device under group address control must have an individual address between 1 and 111 otherwise a fault value of 4 is transmitted. Devices not using the group address facility may be addressed at any address (1–126).

Communication

XP95, Discovery and CoreProtocol compatible

Backward Compatibility

The alarm devices will operate only with control equipment using the Apollo protocols. The features of the Open-area alarm devices are available only when the device is connected to a control panel with the appropriate software.

Product Information

The Intelligent Open-Area Sounder Visual Indicator is designed for use in open areas.

Key Features

For use with XP95 & Discovery systems Self-test fault monitoring IP65 rated Individual and group addressing Synchronisation of flashes Comes with Isolating Base as standard Loop-powered Red and clear lens option

General
WirelessNo
Warranty10 year
Performance
Maximum sound output tone100dB (A)
Selectable volume(s)
  • 92dB (A)
  • 100dB (A)
Tone(s)3
Electrical
Power-up surge current 1.2mA
Maximum power-up time<1 second
Quiescent current330μA
Quiescent current tested at24V dc
Supply voltage (min)17V dc
Supply voltage (max)28V dc
Supply voltage (Vmin-Vmax)17 to 28V dc
PolarityL1 & L2 are polarity sensitive
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Operating temperature (min)-10°C
Operating temperature (max)55°C
Operating temperature-10 to 55°C
IP rating ValueIP65
Conformance
StandardsEN 54-3
Approvals
  • CCMG
  • CPD
  • LPCB
  • VNIIPO
Mechanical
Weight260g
ColourRed
Materials housingPolycarbonate
Product depth97.5mm
Product diameter104mm
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.

2nd Slow Whoop/DIN Tone
Apollo Alert Tone
Apollo Evac Tone
DIN Tone
Slow Whoop Tone