58000-600SIL - SIL Discovery Optical Smoke Detector
The Discovery Optical Smoke Detector operates using the light scatter principle and is ideal for applications where slow-burning or smouldering fires pose a potential risk.
Full Details

Application Environments

Bedrooms

Escape routes

Hospitals

Hotels

Medium to large buildings

Offices

University campuses

Restaurants

Brand Information

Discovery® is a range of high-specification, analogue addressable fire detectors and alarm devices. Discovery detectors offer effective false alarm management by a combination of EN 54 approved operating modes and sophisticated algorithms. Drift compensation further reduces the likelihood of false alarms caused by a build-up of dust in the sensing chamber. In addition to the familiar smoke and heat detectors, the Discovery range features two multisensor detectors. One is an optical/heat multisensor which can be used to protect against many types of fire risk. The other is a carbon monoxide/heat multisensor which protects against both smouldering fires and those generating heat.

Operation

The Discovery Optical Detector has a white moulded polycarbonate case with wind-resistant smoke inlets. The two indicator LEDs are red in alarm. Within the case is a printed circuit board which, on one side, has the light-proof chamber with integral gauze surrounding the optical measuring system and, on the other, the signal processing and communications electronics. An infra-red light emitting diode within its collimator is arrnged at an obtuse angle to the photo-diode. The photo-diode has an integral daylight-blocking filter. The IR LED emits a burst of collimated light every second. In clear air the photo-diode receives no light directly from the IR LED, because of the angular arrangement and the chamber baffles. When smoke enters the chamber it scatters light from the emitter IR LED onto the photo-diode in an amount related to the smoke characteristics and density. The photo-diode signal is processed to provide an analogue value for transmission when the detector is interrogated.

Communication

XP95, Discovery and CoreProtocol compatible

Maintenance & Service

Detectors should be maintained according to BS 5839-1 or other locally applicable code. Test equipment can be ordered from Apollo for testing smoke and heat detectors. Detectors should not be cleaned in the field except for careful removal of exterior dirt with a damp cloth. For cleaning and recalibration detectors should be returned to Apollo Fire Detectors or to the local distributor.

EMC Directive 2014/30/EU

The Discovery Optical Smoke Detector complies with the essential requirements of the EMC Directive 2014/30/EU, provided that it is used as described. A copy of the Declaration of Conformity is available from Apollo upon request. Conformity of the Discovery Optical Smoke detector with the EMC Directive, does not confer compliance with the directive on any apparatus or systems connected to them.

Construction products regulation 305/2011

The Discovery Optical Smoke Detector complies with the essential requirements of the Construction Products Regulation 305/2011/EU. A copy of the Declaration of Performance is available from Apollo upon request.

Product Information

The Discovery Optical Smoke Detector operates using the light scatter principle and is ideal for applications where slow-burning or smouldering fires pose a potential risk.

Key Features

Responds well to slowburning, smouldering fires Well-suited to bedrooms and escape routes Unaffected by wind or atmospheric pressure Five response modes Remote test feature

General
Applications
  • Bedrooms
  • Escape routes
  • Hospitals
  • Hotels
  • Medium to large buildings
  • Offices
  • University campuses
  • Restaurants
Fire TypeSlow burning, smouldering fires
Warranty10 year
Performance
Analogue value nominal4
Analogue value (- tolerance)0
Analogue value (+ tolerance)4
Analogue value23 +0/-4
Alarm level analogue value55
Chamber typeChevron
Electrical
Protocol voltage (min)5V
Protocol voltage (max)9V
Protocol voltage5 to 9V peak to peak
Power-up surge current 1mA
Maximum power-up time10 seconds
Status indicator - AlarmRed
Quiescent current440μA
Quiescent current tested at24V dc
Sampling frequencyOnce per second
Terminal functions +R+R Remote indicator positive connection
Terminal functions -R-R Remote indicator negative connection
PolarityL1 & L2 are polarity insensitive
Alarm current (at 24 volts)3.4mA
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-40°C
Operating temperature (max)70°C
Operating temperature-40 to 70°C
IP rating ValueIP44
Conformance
StandardsEN 54-7
Approvals
  • LPCB
  • ESC
  • CPR
SIL rating2
Mechanical
Weight105g
Materials housingPolycarbonate
Materials terminalsNickel plated stainless steel
Product length42mm
Product diameter100mm
Detection principlePhoto-electric light scattering.
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.