XP95 I.S. Manual Call Point - Yellow

This product is now obsolete

55100-942APO

The Manual Call Point is commonly used to manually control extinguishant release. The Manual Call Point is suitable for use in areas where explosive atmospheres are, or may be, present.

Technical specification
General
Warranty
3 year
Mechanical
Colour
Yellow
Weight
240g
Materials housing
  • Polycarbonate
  • ABS
Product length
97.5mm
Product width
93mm
Product depth
71mm
Detection principle
Operation of a switch.
Key type
KAC Manal Call Point test & reset key
Product length
3.84in
Product width
3.66in
Product depth
2.8in
Conformance
Approvals
BASEEFA
Electrical
Protocol voltage (max)
9V
Protocol voltage (min)
5V
Protocol voltage
5 to 9V peak to peak
Power-up surge current
1mA
Quiescent current
300μA
Quiescent current tested at
24V dc
Polarity
L1 & L2 are polarity sensitive
Environmental
Humidity (max)
95% RH
Humidity (min)
0% RH
IP rating Value
IP67