55000-401APO - XP95 CS Heat Detector
The XP95 Heat Detector monitors temperature by using a single thermistor which provides a count output proportional to the external air temperature. The XP95 range features two heat detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.
Full Details

Application Environments

Car parks/loading bays

Dusty environments

Warehouses

Hotels

Medium to large buildings

Offices

Restaurants

Retail

Brand Information

The XP95 range of analogue addressable fire detectors uses tried and trusted technology to give the best performance, and has unique features that benefit the installer and the end user. It is suitable for medium-to-large applications with simple installation requirements. As it operates using digital communication, XP95 has a high immunity from corruption, and is, therefore, often preferred in a large system where life safety is critical. XP95 products are frequently used in commercial, industrial, financial, government, IT/telecoms and healthcare applications.

Electrical Description

The detectors are designed to be connected to a two wire loop circuit carrying both data and a 17V to 28V dc supply. The detectors are connected to the incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between +R and -R terminals. An earth connection terminal is also provided. When a device is energised the ASIC regulates the flow of power and controls the data processing. The thermistor provides an output over normal operating ranges that is proportional to the external air temperature. This voltage output is processed in the A/D converter and stored by the communications ASIC. It is transmitted to control equipment when the device is interrogated. When a count of 55 is exceeded the alarm flag is initiated and the device address is added to the data stream every 32 polling

Operation

The XP95 heat detectors have a low air flow resistance case made of self-extinguishing white polycarbonate. The devices monitor heat by using a single thermistor network which provides a voltage output proportional to the external air temperature. The standard heat detectors, 55000-400 and 55000-420, respond to increasing air temperature in such a way that they are classified as an A2S device. Both devices will give 55 counts at 55°C. A high temperature CS heat detector, 55000-401, which can be installed in a typical ambient temperature of 55°C is available. This device will give 55 counts at 90°C.

Application

The choice of detector from the XP95 range follows the well established principles of system design. That is, the optimum detector type will depend on the type of fire risk and fire load, and the type of environment in which the detector is sited. For general use, smoke detectors are recommended since these give the highest level of protection. Smoke detectors from the XP95 range may be optical or multisensor types. It is generally accepted that ionisation types have a high sensitivity to flaming fires whereas optical detectors have high sensitivity to smouldering fires. The multisensor is basically an optical smoke detector and will therefore respond well to the smoke from smouldering fires. The detector also senses air temperature. This temperature sensitivity allows the multisensor to give a response to fast burning (flaming) fires. Where the environment is smoky or dirty under normal conditions, a heat detector may be more appropriate. It must be recognised, however, that any heat detector will respond only when the fire is well stablished and generating a high heat output. Unless otherwise specified, devices described in this guide are suitable for indoor use only.

Device Addressing

Each XP95 device responds to interrogation and command from central control equipment. It communicates to the panel information on status, command bits, type, location, and other information that allows an alarm to be raised even when the device is not itself being interrogated. Message error checking is also provided. The devices are compatible with Discovery® systems and control equipment to aid maintenance, extension and upgrade of existing systems. A unique, patented XPERT card provides simple, user friendly and accurate identification of detector location whereby a coded card, inserted in the base, is read by any detector once it is plugged in. All the electronic components are in the detector but the location information is held in the base. The address card simplifies and speeds up installation and commissioning. Addressing errors during maintenance and service are eliminated. The XP95 detectors provide an alarm facility that automatically puts an alarm flag on the data stream and reports its address when the pre-set EN54 thresholds are exceeded. The devices provide great flexibility in system design with the control equipment determining the characteristics of the system. A large and growing range of compatible control equipment is available from many sources - details are available from Apollo on request.

Communication

XP95, Discovery and CoreProtocol compatible

Backward Compatibility

The device is compatible with Series 90, Discovery® and XPlorer systems.

Maintenance & Service

Detectors should be maintained according to BS 5839-1 or other locally applicable code. Test equipment can be ordered from Apollo for testing smoke and heat detectors. Detectors should not be cleaned in the field except for careful removal of exterior dirt with a damp cloth. For cleaning and recalibration detectors should be returned to Apollo Fire Detectors or to the local distributor.

EMC Directive 2014/30/EU

The XP95 Heat Detector complies with the essential requirements of the EMC Directive 2014/30/EU, provided that it is used as described. A copy of the Declaration of Conformity is available from Apollo upon request. Conformity of the XP95 Heat Detector with the EMC Directive, does not confer compliance with the directive on any apparatus or systems connected to it.

Construction products regulation 305/2011

The XP95 Heat Detector complies with the essential requirements of the Construction Products Regulation 305/2011/EU. A copy of the Declaration of Performance is available from Apollo upon request.

Environmental Characteristics

XP95 Standard Heat Detectors operate over the range -20°C to +70°C, the High Temperature Heat Detectors operate over the range –20°C to +120°C. The detectors are unaffected by atmospheric pressure.

Product Information

The XP95 Heat Detector monitors temperature by using a single thermistor which provides a count output proportional to the external air temperature. The XP95 range features two heat detectors, standard and high temperature. The standard heat detector is classified as an A2S device and will report an alarm at 55°C. The high temperature detector, classified as a CS device, will report an alarm at 90°C.

General
Applications
  • Car parks/loading bays
  • Dusty environments
  • Warehouses
  • Hotels
  • Medium to large buildings
  • Offices
  • Restaurants
  • Retail
Warranty10 year
Performance
Analogue value nominal2
Analogue value (- tolerance)2
Analogue value (+ tolerance)2
Analogue value25 +2/-2
Alarm level analogue value55
Chamber typeChevron
Heat classificationCS
Electrical
Protocol voltage (min)5V
Protocol voltage (max)9V
Protocol voltage5 to 9V peak to peak
Power-up surge current 1mA
Maximum power-up time4 seconds
Status indicator - AlarmRed
Status indicator - FaultOff
Quiescent current250μA
Quiescent current tested at24V dc
Supply voltage (min)17V dc
Supply voltage (max)28V dc
Supply voltage (Vmin-Vmax)17 to 28V dc
Sampling frequency+L2 Loop in & out positive, double terminal
Terminal functions L1 in-L1 in Loop in & out, double terminal
Terminal functions +R+R Remote indicator positive connection
Terminal functions -R-R Remote indicator negative connection
PolarityL1 & L2 are polarity insensitive
Alarm current (at 24 volts)2.25mA
Remote LED current4mA
Battery poweredNo
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-20°C
Operating temperature (max)70°C
Operating temperature-20 to 70°C
IP rating ValueIP53
Storage temperature (min)-30°C
Storage temperature (max)80°C
Storage temperature-30 to 80°C
Conformance
StandardsEN 54-5
Approvals
  • SBSC
  • BOSEC
  • CPR
  • KRS
  • LPCB
Mechanical
Weight105g
ColourWhite
Materials housingPolycarbonate
Materials terminalsNickel plated stainless steel
Product length42mm
Product diameter100mm
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.