The XP95A Ionization Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.
Full Details

Application Environments

Bedrooms

Clean rooms

Hotels

Medium to large buildings

Offices

Retail

Brand Information

XP95A uses a ‘central intelligence’ system where all the decisions are made by the control panel. Each detector is addressed using Apollo’s patented XPERT Card and supplied with the mounting bases. The XP95A product line includes an ionization detector, a photo-electric detector, a heat detector, a multisensor, an isolator and a series of modules.

Brand Features

XPERT Card addressing Analog value report Alarm flags for fast alarm response Synchronization of all loop powered notification devices Advanced error check

Product Information

The XP95A Ionization Detector uses a low activity radioactive foil to detect fires by irradiating the air in the smoke chambers and causing a current flow. If smoke enters the chamber, the current flow is reduced leading to an alarm.

Key Features

Responds well to fast-burning, flaming fires Designed to operate in a variety of environments Minimal effects from temperature, humidity, atmospheric pressure

General
Applications
  • Bedrooms
  • Clean rooms
  • Hotels
  • Medium to large buildings
  • Offices
  • Retail
Fire TypeFast burning, flaming fires
Warranty10 year
Performance
Chamber typeChevron
Environmental
Humidity (min)0% RH
Humidity (max)95% RH
Humidity Noteno condensation or icing
Humidity0% to 95% (no condensation or icing)
Operating temperature (min)-4°C
Operating temperature (max)140°C
Operating temperature-4 to 140°C
Storage temperature (min)-22°C
Storage temperature (max)176°C
Storage temperature-22 to 176°C
Conformance
Approvals
  • CSFM
  • FM
  • MSFM
  • SII
  • uL
Mechanical
Weight105g
ColourWhite
Materials housingPolycarbonate
Product diameter100mm
Detection principleIonisation chamber.
Sensor configurationTwin compensating chambers using one single sided ionising radiation source.
Information icon
Please Log in or register for unlocked and editable PDFs, BIM Objects and Product Images.
Data Sheets
Installation Guides
How to Order

Apollo is dedicated to ensuring that our customer service is aligned with your expectations. This includes making our order, service and delivery process a seamless and hassle-free experience.

Full details of our service standards can be downloaded here.

Existing customers

Please email your order to us at: ukorders@apollo-fire.com or tel: 023 9245 6530.

New customers

Please email your order to us at: sales@apollo-fire.com or tel: 023 9244 2700.

Oops…

Despite our best efforts, mistakes sometimes happen. Please contact us at: orderqueries@apollo-fire.com if you have any difficulties placing your order.

Please note…

Remember to quote your account number and purchase order number on any order correspondence.

All orders must be over £50.00 (excluding carriage). Any orders received under the minimum order value will be returned to sender for revision.